2.6 Fuellox System Configuration

2.6 Fuellox Configuration

Once the Fuellox unit is installed, the hardware needs ot be configured. The Fuello App configures the unit.

2.6.1 Configuration Options

FeatureDescriptionDefault Valueunit
Timers
Pre Flow TimeoutTime to start flow once pump starts20sec
Post Flow TimeoutTime to restart flow once pump stops40sec
Residuals TimerTime to detect flow once transaction stops3000milli sec
BT Reconnect TimerTime to reconnect BT if connection is broken3000milli sec
Max Pump Run TimerMAx time for pump active. Creates a pump On/Off duty cycle0 [Disabled]
10 = 10 on, 10, off
Min
IO Options
Nozzle SwitchTrue/False for Nozzle Switch installedFalseBoolean
E-Stop (Open)Normally Open EStop installedFalseBoolean
E-Stop (Close)Normally Closed EStop installedFalseBoolean
OverrideNot Applicable - Future capabilityFalseBoolean
Level Options
Level InstalledLevel instrument installedFalseBoolean
Max LevelMax hight of liquip in mm. usually same as Safe Fill3000mm max
Max AnalogueMax analogue value20mA max
K-Factor
Pulse Meter K-FactorPulses per litre for the Pulse Meter Model
Check your meter instructions.
33 for K-24
106.841 for OM-025
pulse per litre
Untis should be Calibrated by a suitably qualifed service agent.
Other
Illegal VolVolume to detect & log from non authorised pulses.
acts as a noise filter if needed
2000mL
BypassNot Applicable - Future capabilityFalseBoolean
Demo ModeVirtual pulse input. Simulates a pump running.
Used for testing and demos
0 = Off
100 = on
pulse per second

Discuss your settings with the help desk if needed.

Most units arrive to the end user with the default configuration appiled.

To update the Config you must be in Bluetooth range of the unit.

!!! Info You must be in range of the Fuellox device to apply its Configuration.

2.6.1 Accesing the Config Options

Not every user has access to Manage a Fuellox Device. The help desk can provide access to these features when needed. It really designed for installers, resellers and service agents. From time to time a customer may need to edit config. ie to change a timer, or add an estop etc.

If you don’t have the Manage Devices option in your Fuellox Menu call the Help Desk or your reseller.

Manage Device Menu

2.6.2 Manage Device Config Page

Toggle the Bluetooth switch to find your device.

Device Search and Connect

Search for Devices

Tap your device to Connect and open the Config page. The App will need connect to the actuall device.

Should the connection not be completed, just hit Retry

Connect Retry

Retry Connect

!!! Warning If you see a message to PAIR be sure to accept the request.

Once connected the Units Details will be shown

Connected

Device Connected

2.6.3 Apply the Devices Settings

Click the Config Tab

Enter Config Page

Enter the Timeout values, or accept the default values.

Scroll down

2.6.4 Apply the Installation (IO) toggles

Set the nozzle and estops according to the systems installed and wired up.

Enter the Install Options

2.6.5 Apply Level Attributes

Set the Level switch on. Be sure to use an approved level instrument. ie IOTIQ FLX-LVL-JPS3

If you are unsure of the other settings advise the Help Desk and they can make some suggestions to get the system operational.

!!! Note For the Level System to work be sure to choose or upgrade to the ‘FLEET’ service.

Enter Level Attributes

2.6.7 Enter the K-Factor

Enter the kFactor if its not already applied.

If you enter the default value from your pulse meters instructions you will also need to complete a proper calibration.

Some meters are shipped with a calibration certificate [ie Flomec OM-025 variants and Macnaught MX series] and these high end meters are often a much lower cost than the calibration service required for a low cost meter.

Enter the K-Factor

2.6.7 Enter the Optional (Other) Settings

In most cases these settings won;t change and the default values suit 99% of use cases.

Enter the Other Settings

2.6.8 Demo Mode

Demo Mode is useful if a system is to be Configured before the wiring is complete. Enter a value into the Demo Mode field, and this will simulate a virtual pulse meter. When the pump starts (and nollze lifted) the pulses shall commence, and a cirtual fuel dispense shall occcur. This data is posted to the Fuellox Cloud.

Demo transactions can be removed later, jsut advise the help desk and they can schedule the deletion.

2.6.9 Save Changes

Click Save and the updated shall be applied to the Device and Cloud.

Save Changes

2.6.10 Reboot the Device

Once changes are applied, the device must be switched off and rebooted. A power cycle is required at the completion of this process. Failure to reset the device may prevent the device operating with the new Configuration.

!!! Warning The Device must be Power Cycled after the change are appllied .

2.6.11 Calibration

See Here for information on how to start the calibration process.